Hi folks, I got a heat pump installed at my home and I’m looking to better understand when/how it switches over to backup fuel in the winter.
My unit is the LENNOX ELITE EL18XPV SERIES, which I found heating specs on here
It is installed in conjunction with a heating oil fired boiler and an aqua coil as the backup heat source. When it was installed, I asked, and the installer indicated that the heat pump will switch over to the boiler at about 37F. What I don’t fully understand though, is that this unit was billed as a variable speed/inverter, so it seems it should be able to run at lower temperatures than 37. The website above seems to indicate it should produce 31,800 BTU/h at 17F, so can I set the “switch-over” temperature of outside to be lower to use less oil?

  • eramseth@lemmy.world
    link
    fedilink
    English
    arrow-up
    1
    ·
    edit-2
    1 year ago

    You might need to experiment. What sort of thermostat do you have? Ecobee lets you see one single chart which type of heat is being used and the outside and inside temperatures.

    From there you can adjust what temp to skip heat pump and go straight to aux heat so that you aren’t wasting time and energy without making your home any warmer. It will automatically switch over of course if no temperature increase is detected within a set amount of minutes (programmed with some sane defaults of course).

    I have a dual system and part of it was replaced more recently. I found the part of it that’s newer can heat effectively at lower temps. They aren’t the same model or anything though.

  • Jakor@lemmy.world
    link
    fedilink
    English
    arrow-up
    0
    ·
    1 year ago

    I’m on mobile and tbh don’t have time to dig into this too much, but I think you would do well to calculate the point of optimum efficiency for your specific scenario. I am in a similar scenario and hope to put together a spreadsheet that I could share if it doesn’t already exist elsewhere, but here is what I would do:

    1. Find out if your heat pump IOM specifies the minimum ambient temperature before electric auxiliary heat kicks in (sometimes called “em heat” or emergen heat). Electric heat will always be the most expensive source of heat, so you should use oil heat when temperatures drop below that.

    2. Look up the peak electric rate (in $/kW-hr) for your utility company. Use this to calculate the cost, per hour, to run your heat pump in all temperatures tabulated in your link. This will tell you how expensive it is to run your heat pump in a worst-case scenario.

    3. Calculate the cost to run your boiler, per hour. This is where you will have to do your own homework on efficiency of your boiler, rate of consumption, and cost of oil in your location. Hard to say if the boiler will run at full capacity or part load, but most are capable of running between 20-100% of nameplate capacity (5:1 turn-down). Summarize your findings into a coat to run your boiler per hour.

    4. When the answer for #2 exceeds the answer for #3, you’ve identified your switch point! Note that this relies on a number of assumptions, like that the heat pump is running full capacity.

    • bbbbb@lemmy.worldOP
      link
      fedilink
      English
      arrow-up
      1
      ·
      edit-2
      1 year ago

      Ah, ok, good point. In my install, I did not opt to have them wire and install electric auxiliary heating strips for my unit, and the boiler & aqua coil is I believe being controlled by a control system that makes the unit think the boiler is a heating strip. 17 F is about the coldest it got in my climate last winter, so I guess that’s a good starting point.
      So it seems my Heat pump alone would run at 4.2 kW for 31,800 Btu. at 17F. My blended electric rate is about $.12/kwH, so about $.5/hr to run.

      For my house, I believe the load calculation would be that I need about 48,000 Btu to effectively heat. Our boiler runs at 0.75 gal/hr max, and heating oil was $4.69/gallon last winter, so the boiler would still need to run at ~20-25% of capacity(assuming it’s a linear curve) at 17F to reach that btu number based on 138,500btu/gal x 0.75gal/hr x 0.8(not so sure on efficiency) x 20% capacity = 16,620 btu, which I believe at 0.75gal/hr x 0.2 = 0.15gal/hr would be ~$0.72/hr. So that would give me a total cost of ~$1.2/hr for 48,420 btu.

      Without a heat pump, I guess I would solely be burning oil, so that would need to be about 57-60% load, so 138,500btu/gal x 0.75gal/hr x 0.8 x .6=49,860btu, which I believe at 0.75gal/hr x 0.6 = 0.45gal/hr would be ~$2.1/hr.

      It seems like based on my electric rates and the values from that heat pump, it should offset roughly half of my heating oil usage at the 4.2 kW electric consumption assuming the boiler has some sort of ability to modulate oil in take.

  • kamin@lemmy.kghorvath.com
    link
    fedilink
    English
    arrow-up
    1
    ·
    1 year ago

    You can, but the lower you go (usually starting around 30F), performance degrades, with around 15-17F being the lower limit that you can run it in heating mode and still pull heat out of the outside air.

    Ideally your aux heat would only be needed on those more extreme days.